CPD0318
Nuevo
R48-500A * 2 o cambio R48-1000A 200 ~ 250 v AC DC 48 V
The input phase voltage 220 vac
90 vac ~ 290 vac input voltage range
Input frequency 45 hz ~ 65 hz
Dc power distribution:
Advertencia: ¡Últimas unidades en stock!
Fecha de disponibilidad:
NetSure212 C23 Emerson communication power supply adopts embedded installation design, suitable for standard 19 inch rack installation.NetSure212 C23 nominal output voltage: - 48 v, nominal output current: 40 a.System can adapt to the wide range of ac input, intelligent battery management, remote environmental monitoring, etc
2, system technical parameter table
Environmental conditions:
Working temperature 5 ℃ to 40 ℃
Storage temperature - 40 ℃ ~ 70 ℃
Relative humidity 90% RH or less
The altitude 2000 m or less (need) derating use more than
Pollution levels level 2
Other no conductive dust and corrosive gas, no explosion danger
Ac power distribution:
The input phase voltage 220 vac
90 vac ~ 290 vac input voltage range
Input frequency 45 hz ~ 65 hz
Input current largest single-phase input, each input current rectifier module 7 a or less
The power factor of 0.99 or higher
Overvoltage level
Dc power distribution:
Rated output voltage 53.5 Vdc
Range of output voltage 42.3 Vdc ~ 57.6 Vdc
The output current of 40 a
Voltage accuracy + / - 1% or less
The efficiency of 90% or higher
Fengfeng value noise voltage of 200 mv or less
Telephone scale 2 mv or less heavy noise voltage
3, the system characteristics
Use standard 19 inch structure design, with good generality
Small volume, light weight, embedded installation, save installation cost and size of the room
The positive operation, convenient maintenance
A wide range of input voltage power grid adaptable
Wide working temperature range of the rectifier module, environment adaptiveness
No damage hotplug, online maintenance, convenient and quick
With a full range of lightning protection design, providing multi-channel dc power output
Have perfect battery management function, improve the service life of the battery
Offer a variety of RS232, front-end ports, such as dry contact communication interface, flexible networking, can realize remote monitoring
Through the CE, UL, TLC and other related certification at home and abroad
3, specifications:
Rectifier module models: R48-1000 configuration: 1-2, the largest 40 a
Monitoring module models: M522B M523B or M221B standard configuration: 1
Ac power distribution ac input mode: L + N + PE / 220 v
Dc power distribution line 2 load open: 2 x 32 p a / 1